Chlorination is a chemical method for disinfecting water. The chlorine inactivates pathogens in the water and provides a barrier against recontamination. It is normally applied at the last stage of a drinking-water treatment process.  
 
Chlorination is a chemical method for disinfecting water. The chlorine inactivates pathogens in the water and provides a barrier against recontamination. It is normally applied at the last stage of a drinking-water treatment process.  
  
Line 12: Line 12:
 
'''Yield''': Generally, 350–1400 m3 of treated water per kg of a 70% chlorine compound.
 
'''Yield''': Generally, 350–1400 m3 of treated water per kg of a 70% chlorine compound.
  
==Suitable conditions==
+
===Suitable conditions===
 
'''Area of use''': Wherever drinking-water needs to be disinfected and chlorine is available.
 
'''Area of use''': Wherever drinking-water needs to be disinfected and chlorine is available.
  
==Construction, operations and maintenance==
+
===Construction, operations and maintenance===
 
The flow rate of the raw water must be checked and adjusted if necessary, and the chlorine tank must be refilled with a freshly-prepared solution once or twice a week. Operators must be careful to avoid contact with chlorine compounds or solutions, and use protective gloves and utensils to prepare the chlorine solutions. The gloves and utensils will need to be replaced occasionally. In some cases, the amount of chlorine added to the water, together with residual chlorine levels, are recorded in a logbook. Chlorinators must be adjusted and cleaned of chlorine salts regularly, and when the hoses become corroded by chlorine they must be replaced.  
 
The flow rate of the raw water must be checked and adjusted if necessary, and the chlorine tank must be refilled with a freshly-prepared solution once or twice a week. Operators must be careful to avoid contact with chlorine compounds or solutions, and use protective gloves and utensils to prepare the chlorine solutions. The gloves and utensils will need to be replaced occasionally. In some cases, the amount of chlorine added to the water, together with residual chlorine levels, are recorded in a logbook. Chlorinators must be adjusted and cleaned of chlorine salts regularly, and when the hoses become corroded by chlorine they must be replaced.  
  
Line 29: Line 29:
 
Despite these limitations, disinfecting drinking-water by chlorination is one of the most effective and least-expensive technologies available and should be encouraged.
 
Despite these limitations, disinfecting drinking-water by chlorination is one of the most effective and least-expensive technologies available and should be encouraged.
  
==Costs==
+
===Costs===
 
'''Initial cost''': A chlorinator and hoses can cost as little as US$ 15, but there will be additional costs for the tank, for the concentrated chlorine solution, and for the construction costs of a protective shelter.
 
'''Initial cost''': A chlorinator and hoses can cost as little as US$ 15, but there will be additional costs for the tank, for the concentrated chlorine solution, and for the construction costs of a protective shelter.
  
==Field experiences==
+
===Field experiences===
 +
The following project(s) utilize chlorination running through pipes.
 +
<br>
 +
{|style="border: 2px solid #e0e0e0; width: 20%; text-align: justify; background-color: #e9f5fd;"  cellpadding="2"
 +
|- style="vertical-align: top"
 +
|[[Image:akvorsr logo_lite.png|center|60px|link=http://akvo.org/products/rsr/]]
 +
|- style="vertical-align: bottom"
 +
|[[Image:project 786.jpg |thumb|center|140px|<font size="2"><center>[http://rsr.akvo.org/project/786/ RSR Project 786]<br>MWA-LAP: <br>Honduras</center></font>|link=http://rsr.akvo.org/project/786/ ]]
 +
|}
  
{|style="width: 70%; text-align: justify; background-color: #f5f5f5;"
+
<br>
|[[Image:rsr 786.jpg|thumb|none|200px|<font size="2"><center>Project 786</center></font>|link=http://www.akvo.org/rsr/project/786/]]
 
|'''AKVO RSR Project:''' [http://www.akvo.org/rsr/project/786/ MWA-LAP: Honduras]
 
In Honduras, MWA member Water For People will be implementing the program in the municipality of San Antonio de Cortes. Consisting of 36 villages and 11 urban neighborhoods, the region has an area of 227 square kilometers with a population of 30,000.
 
|}
 
  
==Acknowledgements==
+
===Acknowledgements===
 
* Brikke, François, and Bredero, Maarten. [http://www.washdoc.info/docsearch/title/117705 Linking technology choice with operation and maintenance in the context of community water supply and sanitation: A reference document for planners and project staff] or ([http://www.who.int/water_sanitation_health/hygiene/om/wsh9241562153/en/ alternative link]). World Health Organization and IRC Water and Sanitation Centre. Geneva, Switzerland 2003.
 
* Brikke, François, and Bredero, Maarten. [http://www.washdoc.info/docsearch/title/117705 Linking technology choice with operation and maintenance in the context of community water supply and sanitation: A reference document for planners and project staff] or ([http://www.who.int/water_sanitation_health/hygiene/om/wsh9241562153/en/ alternative link]). World Health Organization and IRC Water and Sanitation Centre. Geneva, Switzerland 2003.

Latest revision as of 02:34, 7 May 2015

Chlor pipe icon.png
Floating bowl chlorinator can be placed in tanks or reservoirs. Photo: WHO.
A type of floating chlorinator.

Chlorination is a chemical method for disinfecting water. The chlorine inactivates pathogens in the water and provides a barrier against recontamination. It is normally applied at the last stage of a drinking-water treatment process.

The most frequently used low-cost technology methods are batch chlorination and flow chlorination. For batch chlorination, a concentrated chlorine solution is added to the water in a reservoir, with both inlets and outlets closed. The water is stirred and the chlorine is left to react for at least 30 minutes. After that, the outlets can be opened. When the reservoir is empty, the outlets are closed and the reservoir is refilled with a new batch of water to be disinfected.

Flow chlorinators (also called drip-feed chlorinators or constant head chlorinators) continuously feed small quantities of a weak chlorine solution to a flow of fresh water, often at the inlet of a clear-water reservoir. Usually, a small reservoir containing the chlorine solution is placed on top of the water reservoir and the solution is administered close to the point where fresh water comes in, and turbulence guarantees good mixing. A special device, such as the floating bowl chlorinator, enables precise dosage. Sometimes a special electric pump is used for this purpose. Electrical devices that convert a solution of kitchen salt to active chlorine can be purchased for on-site chlorine production. Small test kits are also available for monitoring and for adjusting chlorine doses to the water quality and quantity. Chlorine-producing compounds must always be stored and prepared with care.

Yield: Generally, 350–1400 m3 of treated water per kg of a 70% chlorine compound.

Suitable conditions

Area of use: Wherever drinking-water needs to be disinfected and chlorine is available.

Construction, operations and maintenance

The flow rate of the raw water must be checked and adjusted if necessary, and the chlorine tank must be refilled with a freshly-prepared solution once or twice a week. Operators must be careful to avoid contact with chlorine compounds or solutions, and use protective gloves and utensils to prepare the chlorine solutions. The gloves and utensils will need to be replaced occasionally. In some cases, the amount of chlorine added to the water, together with residual chlorine levels, are recorded in a logbook. Chlorinators must be adjusted and cleaned of chlorine salts regularly, and when the hoses become corroded by chlorine they must be replaced.

If a steel chlorine tank is used, it must be painted and checked for corrosion every year, and the shelter for the chlorine tank needs to be maintained. Usually, the water committee appoints a caretaker who is trained for such work. The chlorine compound itself must be obtained from a merchant or the health department, and an adequate supply of chlorine compound must be kept in stock. An external organization, such as a government health or water department, will provide training for caretakers and perform monitoring.

Potential problems
— chlorination is less effective in alkaline water (pH above 8.0);
— when the water contains excessive organic matter or suspended material, it will need to be pretreated;
— the cost and availability of chlorine compounds can be serious limitations;
— chlorination affects the taste of water and for this reason the water may be rejected by consumers who have not been informed;
— on the other hand, users may believe a chlorine taste indicates that the water has been disinfected, but water can still taste of chlorine even when not enough has been added to purify it.

Despite these limitations, disinfecting drinking-water by chlorination is one of the most effective and least-expensive technologies available and should be encouraged.

Costs

Initial cost: A chlorinator and hoses can cost as little as US$ 15, but there will be additional costs for the tank, for the concentrated chlorine solution, and for the construction costs of a protective shelter.